Tokyo Fuchu Data Center
Fuchu City, Tokyo
From standard racks to products for high-load GPUs. Power and cooling methods can be verified for each product.
Capacity4,000 racks
Rack powerHigh-load product: up to 30 kVA / rack
Cooling methodAir-cooled, rear-door water-cooled, DLC
Published specifications
- Cabinet capacity
- 4,000rackFacility capacity scale, approximate number
- receiving power
- 50MWMaximum power receiving capacity
- standard rack height
- 46UStandard colocation
- standard rack power
- 7 / 15kVA/rackBy service category
- backup runtime
- 48hourGenerator operation using stockpiled fuel
- Cooling
- Wall-mounted blow air conditioning, hot aisle containment. DLC available as a separate productBy product
- dlc power
- 150kVA/rackDLC service maximum value · The announcement for F4 is 150 kW. The unit difference is retained unresolved and not automatically converted.
- dlc lead time
- 2monthShortest lead time · Not a guarantee of individual delivery times
- remote operations
- Deployment, server construction, recovery support, routine operationsOn-site operational services
Services and product specificationsConditions apply to each product or area and may not represent the entire facility.
High-load colocation
- rack power standard
- 15kVA/rackHigh-load product, announced 2025-01-15
- rack power max
- 30kVA/rackHigh-load product maximum value
- rack height
- 50UHigh-load product
- rack load
- 1,050kgHigh-load product
- Cooling
- Rear-door water-cooled air conditionerHigh-load product
- rack count at release
- 100rackProvision scale as of 2025-01-15, approximate number
- planned rack count
- 230rackFinal plan
Differences between published sources
- Unit difference between 150 kVA on the official DLC page and 150 kW in the announcement
- Standard 46U and DLC page 47U are managed by product
Notes
- 2026-09-19 addendum: DC business succession on 2026-04-01 confirmed in F5.
Public web form dedicated to the data center. No login required for new inquiries; existing contractors are routed to the customer portal. Operates by entering the service, purpose, and details and awaiting a response from a representative, with no automated pricing provided. Presence of CAPTCHA at submission requires confirmation.
SourcesPublic sources supporting this listing
- Source 1www.idcf.jp/datacenter/location/fuchu/Checked 2026-09-19
- Source 2tools.idcf.jp/datacenter/colocation/dlc.html?bid=fuchuChecked 2026-09-19
- Source 3www.idcf.jp/pdf/pressrelease/trtvlv00000v21ye-att/IDCF20250707_DLC.pdfChecked 2026-09-19
- Source 4www.idcf.jp/datacenter/location/Checked 2026-09-19
- Source 5www.idcf.jp/news/newsrelease/20250115001/Checked 2026-09-19