Published specificationsOperation announced
netXDC Inzai Campus
Inzai City, Chiba Prefecture
3-building campus in Inzai City. Current official specifications show a total rack equivalent of 4,400, employing different cooling systems per building.
Capacity4,400 racks
Rack powerSI3 total electrical capacity 20MW (not IT capacity)
Cooling methodSI1/SI2 central water-cooled, SI3 air-cooled free-cooling chillers
Published specifications
- Cabinet capacity
- 4,400rackTotal across SI1 to SI3 · Simple sum: 1,200 for SI1, 1,600 for SI2, 1,600 for SI3
- si3 total electrical capacity
- 20MWSI3 total electrical capacity · Not clearly specified as IT capacity
- Cooling
- SI1 central water-cooled N+1, SI2 central water-cooled N+2, SI3 air-cooled free-cooling chillers N+1 (N+2 optional)By building
- backup runtime
- 72hourIn-house private generators per building, unrefueled
Notes
- Because SI3's 20MW is total electrical capacity, it was not adopted for qualification.it_capacity_mw.
- Basis for medium-scale or larger adoption: Confirmed rack equivalents of 1,200 for SI1, 1,600 for SI2, and 1,600 for SI3 on the current official campus page, meeting the criteria even for each building alone.
Dedicated netXDC form. Options include quotes, site tours, and information requests