TELEHOUSE TOKYO Tama 3

Tama City, Tokyo

Opened in 2016 in Tama City. Approximately 1,300 racks, 14 MW facility total. Design PUE 1.31, up to 42 kVA/rack (design value).

ContactOfficial websiteChecked 2026-09-25
Capacity1,300 racks
Rack powerMaximum rated 42 kVA (effective 30 kVA)/rack, average rated 21 kVA (effective 15 kVA)/rack
Cooling methodAir-cooled modular chiller, underfloor air discharge

Published specifications

Cabinet capacity
1,300rackFacility · Approximate number
it capacity
14MWSupplied power for the entire facility
rack power max designed
42kVA/rackMaximum rating · Effective is 30 kVA/rack
rack power average designed
21kVA/rackAverage rating · Effective is 15 kVA/rack
Cooling
Air-cooled modular chiller system, underfloor air dischargeFacility · Air conditioning unit configuration N+2, UPS equipped
design pue
1.31Design value for Tama 3 · Not an operational historical value

Notes

  • 14 MW is for the standalone facility and is not the total for the Tama campus.
  • Basis for medium-scale or larger adoption: Confirmed via official KDDI sources of approximately 1,300 racks and an overall 14 MW, meeting both rack count and IT power criteria.